Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T11CM01281
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/08/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
08/16/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK FRONT WALL 2) INTERIOR SIGNS TO LISTED 600.3 AND MARKED 600.4 |
|
08/15/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
08/10/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK TUX COUNTER AND UNDER FLOOR TO TUX RENTAL 2) OK WEST WALL AND OK 5 WAY MIRROR AREA EX LIGHTS 3) ATTACH FIXTURES SECURELY TO GRID 410.16 4) SUPPORT VDV CABLING 725.3 & 8, 800.3 &24 AND 300.11 5) FILL UNUSED OPENINGS IN JUNCTION BOX-NOT OLD FITTINGS 6) SUPPORT M/C CABLE PER 330.30 7) NEED SUPPORT WIRES FOR RECESSED CANS, EXIT LIGHTS AND 2 X 4'S RELOCATED 8) SUPPORT TRAC LIGHTING 1 PER 4' WITH SUPPORT WIRE 410.104 9) OPEN JUNCTION BOXES-CLOSE 10) CANNOT HAVE CORD HIDDIN IN WALL 400.7 & 8 |
|
07/29/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS IN BACK OF STORE |
|
07/28/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO COMPLIANCE LAST INSPECTION |
|
07/27/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) PROTECT VDV CABLING FROM SHARP METAL EDGES AND TO CLOSE TO EDGE 2) NOTE: 725.3 & 8, 800.3 & 24 AND 300.11 WILL APPLY 3) FINISH M/C CABLE |