Permit: T11CM01281

Parcel: 10509546D


Addresses:

90 W RIVER RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T11CM01281

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/08/2011 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/16/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK FRONT WALL
2) INTERIOR SIGNS TO LISTED 600.3 AND MARKED 600.4
08/15/2011 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
08/10/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TUX COUNTER AND UNDER FLOOR TO TUX RENTAL
2) OK WEST WALL AND OK 5 WAY MIRROR AREA EX LIGHTS
3) ATTACH FIXTURES SECURELY TO GRID 410.16
4) SUPPORT VDV CABLING 725.3 & 8, 800.3 &24 AND 300.11
5) FILL UNUSED OPENINGS IN JUNCTION BOX-NOT OLD FITTINGS
6) SUPPORT M/C CABLE PER 330.30
7) NEED SUPPORT WIRES FOR RECESSED CANS, EXIT LIGHTS AND 2 X 4'S RELOCATED
8) SUPPORT TRAC LIGHTING 1 PER 4' WITH SUPPORT WIRE 410.104
9) OPEN JUNCTION BOXES-CLOSE
10) CANNOT HAVE CORD HIDDIN IN WALL 400.7 & 8
07/29/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS IN BACK OF STORE
07/28/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO COMPLIANCE LAST INSPECTION
07/27/2011 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) PROTECT VDV CABLING FROM SHARP METAL EDGES AND TO CLOSE TO EDGE
2) NOTE: 725.3 & 8, 800.3 & 24 AND 300.11 WILL APPLY
3) FINISH M/C CABLE