Permit: T11CM01276

Parcel: 10408093B


Addresses:

625 W AUTO MALL DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/16/2012 MECHANICAL - FINAL Approved
02/14/2012 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE AUDIBLE AND VISIBLE ALARMS FOR ALL DUCT SMOKE DETECTORS. SEE SECTION 606.4.1 2006 IMC
2) PROVIDE A PROTECTIVE COATING ON ALL EXPOSED ARMAFLEX
3) 1/2" I.D. X 36" GAS FLEX NOT ADEQUATE FOR 150,000 BTU
4) 3/8" I.D. X 18" GAS FLEX NOT ADEQUATE FOR 125,000 BTU
5) AIR BALANCE REPORT OK
12/15/2011 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
12/14/2011 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*