Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/16/2012 | MECHANICAL - FINAL | Approved | ||
| 02/14/2012 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE AUDIBLE AND VISIBLE ALARMS FOR ALL DUCT SMOKE DETECTORS. SEE SECTION 606.4.1 2006 IMC 2) PROVIDE A PROTECTIVE COATING ON ALL EXPOSED ARMAFLEX 3) 1/2" I.D. X 36" GAS FLEX NOT ADEQUATE FOR 150,000 BTU 4) 3/8" I.D. X 18" GAS FLEX NOT ADEQUATE FOR 125,000 BTU 5) AIR BALANCE REPORT OK |
|
| 12/15/2011 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 12/14/2011 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |