Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/10/2012 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 01/03/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) VDV CABLING 725.3 & 8, 800.3 & 24 AND 300.11 2) CANNOT HAVE CORDS ABOVE CEILING 400.7 & 8 3) DUCT ABOVE CEILING AT AUTO BODY REPAIR OFFICES OK TO COVER 3) BOX OVERFILLED 4) OK TILE EXCEPT AS NOTED 153, 154, 155, 157, 158, 159 & 160 |
|
| 12/27/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) DUCT ABOVE CEILING AT PARTS DEPT OK TO COVER |
|
| 12/21/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE SECONDARY DRAINS ON FAN COILS 2) DUCT NOT INSULATED 3) GRID WIRE BLOCKING FILTER WHOLESALE 4) FILTER DOOR MISISNG AND NO FILTER WHOLESALE 2 5) OK TO ROCK WOMEN'S RESTROOMS |
|
| 12/15/2011 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 12/14/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 12/02/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) DUCT ABOVE 2ND FLOOR RESTROOM HARD LIDS OK TO COVER |
|
| 11/30/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) EXTEND VENTS ON CONDENSATE DRAINS ABOVE DRAIN PANS IN FAN COILS 2) PROVIDE OVERFLOW SENSORS 3) OK TO INSULATE DRAIN LINES AND REFER LINES 4) PROVIDE OUTSIDE AIR FOR FAN COIL B & C OK CEILING TILES SERVICE DEPT OFFICES |
|
| 11/08/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) DUCT ABOVE CEILING 2ND FLOOR OK TO COVER 2) EXPANSION AREA AND CLOSING OFFICES 1ST FLOOR, DUCT OK TO COVER |