Permit: T11CM01251

Parcel: 123080450


Addresses:

2732 E HELEN ST #01

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
08/11/2011 MECHANICAL - INTERMEDIATE Approved
08/01/2011 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXTEND ARMAFLEX TO COVER ALL OF SUCTION LINE
2) INSULATE SHEET METAL SUPPLY DUCT AT TOP OF COIL
3) ARMAFLEX MUST BE MINIMUM 6" FROM SINGLE WALL VENT CONNECTOR
4) PROVIDE A PROTECTIVE COATING ON ALL EXPOSED ARMAFLEX