Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/29/2011 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 06/22/2011 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLUMBERS TAPE IS NOT AN APPROVED PIPING SUPPORT 2) FAILURE TO COMPLY WILL RESULT IN RE-FEES |
|
| 06/10/2011 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REMOVE EXCESS FLEX FROM SOLDER JOINTS NOTE: ALL PIPING SHALL BE REAMED 2) SUPPORT PIPE AND TUB WITH PROPERLY SIZED AND INSTALLED CLAMPS 3) INSTALL PIPE INSULATION IN A WORKMAN SHIP LIKE MANNER 4) MANOR AS PRESCRIBED BY THE MANUFACTURE 5) APPARENT CROSS CONNECTION NOT SHOWN ON 09 300 PLAN 6) CORRECT LEAK |
|
| 05/04/2011 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CORRECT SOLDER CONNECTION AT MIXING VALVE-PROPER USE OF FITTINGS 2) SUPPORT ALL PIPING WITH APPROVED PIPING SUPPORTS 3) CORRECT GAS WATER HEATER RELIEF DRAIN PIPING 4) REMOVE TAPE AT B-VENT CONNECTION 5) CORRECT PIPE INSULATION 6) ADJUST MIXING VALVE FOR HOME OWNER |