Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/20/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/08/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/12/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) JAVALINA CANTINA BATHROOM AND HALLWAY EM LIGHTS & POWER OK ONLY 2) 1ST PHASE OK |
|
| 07/11/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 07/08/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CAN LIGHTS LAY ON TILE-NO SUPPORT, SECURE TO T-BAR 2) J-BOXES NOT SUPPORTED-MC MUST BE SUPPORTED WITHIN 12" OF BOX TERM. PER CODE 3) MISSING EM LIGHT IN 4) NEW SONCE LTG. NOT INSTALLED 5) THIS INSPECTION IS FOR THE JAVALINA RESTROOMS ONLY |
|
| 07/07/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUPPORT FOR J-BOXES 2) M/C CABLE NOT TO BE SUPPORTED BY SISMEC WIRES FOR T-BAR, MUST HAVE OWN SUPPORT WIRES 3) MORE THAN ONE TURN OR TWIST OF WIRE SUPPORTS 4) THIS INSPECTION IS FOR RESTROOM AT JAVALINA CANTINA ABOVE CEILING |