Permit: T11CM01221

Parcel: 12616319D


Addresses:

445 S ALVERNON WY

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/20/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/08/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/12/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) JAVALINA CANTINA BATHROOM AND HALLWAY EM LIGHTS & POWER OK ONLY
2) 1ST PHASE OK
07/11/2011 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/08/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CAN LIGHTS LAY ON TILE-NO SUPPORT, SECURE TO T-BAR
2) J-BOXES NOT SUPPORTED-MC MUST BE SUPPORTED WITHIN 12" OF BOX TERM. PER CODE
3) MISSING EM LIGHT IN
4) NEW SONCE LTG. NOT INSTALLED
5) THIS INSPECTION IS FOR THE JAVALINA RESTROOMS ONLY
07/07/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SUPPORT FOR J-BOXES
2) M/C CABLE NOT TO BE SUPPORTED BY SISMEC WIRES FOR T-BAR, MUST HAVE OWN SUPPORT WIRES
3) MORE THAN ONE TURN OR TWIST OF WIRE SUPPORTS
4) THIS INSPECTION IS FOR RESTROOM AT JAVALINA CANTINA ABOVE CEILING