Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/13/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) CALLED CONTRACTOR PER REQUEST-NO RETURN CALL 2) RESCHEDULE INSPECTION 3) OK NORTH BANQUET RESTROOMS |
|
| 09/08/2011 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SESMIC WIRE TO BE STRAPPED TO TEE BAR CEILING 410.16 (C) 2) LOW VOLTAGE TO BE STRAPPED OR REMOVED 720.11 3) MC CABLE TO BE OFF TEE BAR CEILING 4) BOXES TO BE CLOSED UP |
|
| 08/03/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) WALLS OK 2) WHERE ARE ELECTRICAL NOTES |