Permit: T11CM01221

Parcel: 12616319D


Addresses:

445 S ALVERNON WY

Inspection Status: Partial Approval

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
09/13/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) CALLED CONTRACTOR PER REQUEST-NO RETURN CALL
2) RESCHEDULE INSPECTION
3) OK NORTH BANQUET RESTROOMS
09/08/2011 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SESMIC WIRE TO BE STRAPPED TO TEE BAR CEILING 410.16 (C)
2) LOW VOLTAGE TO BE STRAPPED OR REMOVED 720.11
3) MC CABLE TO BE OFF TEE BAR CEILING
4) BOXES TO BE CLOSED UP
08/03/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) WALLS OK
2) WHERE ARE ELECTRICAL NOTES