Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/23/2011 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 05/05/2011 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SECURE ALL PIPING AND TUBING AT CORRECT INTERVALS 2) PROVIDE 6" CLEARANCE FROM VENT CONNECTOR AND COMBUSTIBLE MATERIAL 3) PROVIDE PROTECTION BARRIER FROM AUTO IMPACT 4) INSTALL ROOF FLASHING PER APPROVED PLAN AND MANUFACTURE INSTRUCTIONS AND SEAL EDGES & NAILS TO MAKE WEATHER TIGHT 5) PIPING IN ATTIC TO BE SECURED AT CORRECT INTERVALS AND DRAIN BACK TO TANK OR PROVIDE PROOF OF FREEZE PROTECTION 6) CONTRACTOR TO PAY REINSPECTION FEE PRIOR TO FINAL INSPECTION 7) T & P DRAIN AND PRESURE RELIEF DRAIN TO BE SEPERATE OR UPSIZED TO MEET CROSS SECTIONAL AREA |