Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/13/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 06/06/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* EXTEND VENT IN CONDESATE DRAIN ABOVE DRAIN PAN IN COIL CABINET. PROVIDE SEDIMENT TRAP AT WATER HEATER. LINE SET STILL MISSING ARMFLEX. T + P DRAIN CANNOT BE REDUCED FROM 3/4" I.D. PROVIDE ROOF JACK + FITTING FOR CONDENSATE TERMINATION. |
|
| 06/01/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX AND REMOVE ANY DUCT TAPE USED OUTDOORS 2) CONDENSOR OVERFUSED 3) PROVIDE SEDIMENTS AT FURNACE AND WATER HEATER 4) PVC CANNOT BE WITHIN 6" OF SINGLE WALL VENT CONNECTOR 5) PROVIDE AN OVERFLOW SENSOR 6) TERMINATE T & P DRAIN SEPERATELY FROM CONDENSATE 7) DO NOT USE FLEX COPPER IN T & P DRAIN 8) EXTEND CONDENSATE VENT ABOVE DRAIN PAN 9) COVER ALL SECTIONS OF SUCTION LINE WITH ARAMFLEX 10) PROVIDE 3 SCREWS IN ALL JOINTS OF VENT CONNECTORS 11) REMOVE ALL TAPE |