Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T11CM01173
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/31/2011 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
05/26/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) ICE BIN DRAIN-PVC NOT PRIMED OR SOLVENT WELDED OPEN DRAIN 2) VENT FITTINGS BELOW THE FLOOD RIM TO BE DRAINAGE TYPE 3) WHERE A VENT CONNECTS TO A HORIZONTAL DRAIN IT SHALL HAVE ITS INVERT TAKEN OFF ABOVE THE DRAINAGE CENTER LINE DOWN STREAM OF THE TRAP BEING SERVED 4) ICE MAKER REQUIRES BACKFLOW PROTECTION |
|
05/24/2011 | PLUMBING - FINAL | Not ready for Inspection | 1) EACH FIXTURES TRAP SHALL HAVE A CONNECTING VENT CONNECTED DOWNSTREAM OF THE TRAP 2) ONLY ONE TRAP ON A TRAP ARM 3) USE OF AIR ADMITTANCE VALVES SHOULD BE OK 4) AIR GAPS STRICKLY ENFO 5) CONNECT ICE MAKER |
|
05/18/2011 | PLUMBING - FINAL | Cancelled | CANCELED PER CONTACTOR JOHN ALLEN #975-6162 | |
05/18/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) DOOR LOCKED |