Permit: T11CM01173

Parcel: 125090230


Addresses:

2545 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/07/2011 ELECTRIC - INTERMEDIATE Approved
06/02/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEALS TO BE NON COMBUSTIBLE AND AT BARRIER 300.7
2) UN-NECESSARY INDSPECTIONS MAY RESULT IN REFEE
ROOF:
1) MAINTAIN WORKING CLEARANCES 110.26
2) TIGHTEN LOOSE FITTINGS
3) 60 AMP DISCONNECT LUG DAMAGED DUE TO ARC CONDITION
4) NEED ANTI-OXIDE COMPOUND ALL ALUMINUM CONDUCTORS
5) PROTECT CONDUCTORS 300.4
6) LABEL DISCONNECTS
06/01/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) WHERE ARE DISCONNECTING MEANS INSIDE OF WALK INS FOR UNITS ?
2) RACEWAY SEALS TO BE PER 300.7, ALSO SEAL SEAL TITE RACEWAY
3) SUPPORT SEAL TITE AND M/C ON TOP OF BOXES