Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T11CM01173
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/07/2011 | ELECTRIC - INTERMEDIATE | Approved | ||
06/02/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEALS TO BE NON COMBUSTIBLE AND AT BARRIER 300.7 2) UN-NECESSARY INDSPECTIONS MAY RESULT IN REFEE ROOF: 1) MAINTAIN WORKING CLEARANCES 110.26 2) TIGHTEN LOOSE FITTINGS 3) 60 AMP DISCONNECT LUG DAMAGED DUE TO ARC CONDITION 4) NEED ANTI-OXIDE COMPOUND ALL ALUMINUM CONDUCTORS 5) PROTECT CONDUCTORS 300.4 6) LABEL DISCONNECTS |
|
06/01/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) WHERE ARE DISCONNECTING MEANS INSIDE OF WALK INS FOR UNITS ? 2) RACEWAY SEALS TO BE PER 300.7, ALSO SEAL SEAL TITE RACEWAY 3) SUPPORT SEAL TITE AND M/C ON TOP OF BOXES |