Permit: T11CM01171

Parcel: 140140480


Addresses:

5410 S PINE WY

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/01/2013 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/15/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
05/25/2011 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
05/12/2011 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) NO ONE ON SITE
04/27/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DISCONNECT IN CLOSET NOT PROPERLY WIRED
2) PROVIDE BUSHING WHERE WIRING ENTERS OR EXITS DISCONNECT BOX
3) PROVIDE MINIMUM R-8 (2") DUCT LINER ON ROOF
4) PROVIDE 8' 4X4 UUNDER UNIT (X2) FOR PROPER SUPPORT
5) CONDENSATE NOT INSTALLED IN AN APPROVED MANNER 1, NO P-TRAP, NO PRIMER, NO GLUE, NO U.V. PROTECTION, NO BLOCKING MUST TERMINATE WITHIN 6" OF GRADE AND ELBOW AWAY FROM BURDINL
6) PROVIDE SERVICE OUTLET ON ROOF WITHIN 25' OF UNIT
7) ELEC CONDUIT NOT PROPERLY BLOCKED UP
8) UNIT WIRE SIZE IS TOO SMALL
9) UNIT DATA PLATE NOT PROPERLY IDENTIFIED
10)PROVIDE MEANS OF DISCONNECT WITHIN SIGN & OF UNIT (ON ROOF)
11) ONLY REDWOOD OR PRESSURE TREATED LUMBER TO BE USED ON ROOF