Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/01/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/15/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 05/25/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/12/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NO ONE ON SITE |
|
| 04/27/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DISCONNECT IN CLOSET NOT PROPERLY WIRED 2) PROVIDE BUSHING WHERE WIRING ENTERS OR EXITS DISCONNECT BOX 3) PROVIDE MINIMUM R-8 (2") DUCT LINER ON ROOF 4) PROVIDE 8' 4X4 UUNDER UNIT (X2) FOR PROPER SUPPORT 5) CONDENSATE NOT INSTALLED IN AN APPROVED MANNER 1, NO P-TRAP, NO PRIMER, NO GLUE, NO U.V. PROTECTION, NO BLOCKING MUST TERMINATE WITHIN 6" OF GRADE AND ELBOW AWAY FROM BURDINL 6) PROVIDE SERVICE OUTLET ON ROOF WITHIN 25' OF UNIT 7) ELEC CONDUIT NOT PROPERLY BLOCKED UP 8) UNIT WIRE SIZE IS TOO SMALL 9) UNIT DATA PLATE NOT PROPERLY IDENTIFIED 10)PROVIDE MEANS OF DISCONNECT WITHIN SIGN & OF UNIT (ON ROOF) 11) ONLY REDWOOD OR PRESSURE TREATED LUMBER TO BE USED ON ROOF |