Inspection History: ELECTRIC - TEMPORARY SERVICE

Permit Number - T11CM01166

Inspection Description - ELECTRIC - TEMPORARY SERVICE

Inspection Status - Approved

Date Description Inspector Results Comments
03/28/2012 ELECTRIC - TEMPORARY SERVICE Approved
05/31/2011 ELECTRIC - TEMPORARY SERVICE Partial Approval IVRS - Inspection :*
05/25/2011 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MANUFACTURES HOLDOWN NEEDED FOR BACK FED BREAKER
2) TIGHTEN GROUND RELIEF FITTING
3) CLEAN SURFACE UNDERGROUND BAR 250.12
4) CANNOT USE SHEET METAL THREAD SCREWS FOR GROUNDING 250.8
5) NEED GROUNDING EQUIPMENT ? 250.32
6) ABOVE GRADE (ON ROOF) SCHEDULE 80 PER CITY AMENDMENTS
7) SUPPORT VDV CABLING OF ROOF 725.8 & 800.24
05/24/2011 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LISTED BRACING MISSING ON TRAILER AND BLDG LOW VOLTAGE
2) 3' WORKING CLEARANCE FOR PANELS MISSING IN BLDG AND STRUT STRAP ON PIPE 3' FROM PANEL
3) GROUNDING IN MAIN PANEL NOT NOTED ON PRINT