Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
Permit Number - T11CM01166
Inspection Description - ELECTRIC - TEMPORARY SERVICE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/28/2012 | ELECTRIC - TEMPORARY SERVICE | Approved | ||
05/31/2011 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* | |
05/25/2011 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MANUFACTURES HOLDOWN NEEDED FOR BACK FED BREAKER 2) TIGHTEN GROUND RELIEF FITTING 3) CLEAN SURFACE UNDERGROUND BAR 250.12 4) CANNOT USE SHEET METAL THREAD SCREWS FOR GROUNDING 250.8 5) NEED GROUNDING EQUIPMENT ? 250.32 6) ABOVE GRADE (ON ROOF) SCHEDULE 80 PER CITY AMENDMENTS 7) SUPPORT VDV CABLING OF ROOF 725.8 & 800.24 |
|
05/24/2011 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LISTED BRACING MISSING ON TRAILER AND BLDG LOW VOLTAGE 2) 3' WORKING CLEARANCE FOR PANELS MISSING IN BLDG AND STRUT STRAP ON PIPE 3' FROM PANEL 3) GROUNDING IN MAIN PANEL NOT NOTED ON PRINT |