Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T11CM01142
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/13/2011 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
06/10/2011 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) VDV CABLING TO BE PER 725.3 & 8, 800.3 & 24 AND 300.11 2) SUPPORT MC CABLE 12" OF BOXES AND UPON EXITING WALL-DO NOT LAY ON GRID 300.11 AND 330.17 & 30 3) USE #12 SESMIC WIRE NOT THHN FOR TRACK LIGHT |
|
05/04/2011 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LEAVE TILES OPEN, PROVIDE LADDER FOR INSPECTION |