Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T11CM01131
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/06/2011 | MECHANICAL - FINAL | Approved | ||
10/05/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* CAPTURE & CONTAINMENT ON ALL HOODS OK HEAT SENSOR TEST OK CANNOT CONFIRM MAKEUP AIR TO REAR HOOD PROVIDE AIR BALANCE REPORT AND PLAN REVISION SEE BUILDING INSPECTOR FOR TCO |
|
10/04/2011 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |