Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/19/2011 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 11/16/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) ABOVE CEILING NORTH HALF OF BLDG OK 2) DUCT IN MRI ROOM OK TO COVER 3) PROVIDE A LETTER FROM THE ENGINEER IF DELETING DUCT SMOKE DETECTORS 4) DETECTORS NOT REQUIRED IN UNITS JUST BECAUSE THEY SUPPLY AIR TO COMMON SPACE, ONLY REQUIRED IF THEY SHARE COMMON PLENIUM IN EXCESS OF 2,000 CFM OF RETURN AIR |