Permit: T11CM01119

Parcel: 13317062A

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
12/19/2011 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
11/16/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) ABOVE CEILING NORTH HALF OF BLDG OK
2) DUCT IN MRI ROOM OK TO COVER
3) PROVIDE A LETTER FROM THE ENGINEER IF DELETING DUCT SMOKE DETECTORS
4) DETECTORS NOT REQUIRED IN UNITS JUST BECAUSE THEY SUPPLY AIR TO COMMON SPACE, ONLY REQUIRED IF THEY SHARE COMMON PLENIUM IN EXCESS OF 2,000 CFM OF RETURN AIR