Permit: T11CM01119

Parcel: 13317062A

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
09/28/2011 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
09/14/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SIZE PER PLAN, ALLOW FOR PIPE INSULATION
2) SECURE TRAP PRIMERS
3) INSTALL SAFETY PLATES
4) WEIR OF TRAP MAY NOT BE ABOVE POINT OF VENT
5) ISOLATION VALVE SHOWN ON BRANCH TO TOILET ?
6) SUPPORT ABS REVENTS
7) MAKE CLEANOUT ACCESSIBLE
8) INSTALL BACKING
9) ISOLATION BETWEEN METAL AND COPPER
10) 2 HOLE CLAMPS ON VENT RISERS
11) SWEEPS REQUIRED ON TRAP ARMS
13) DWV TEST THRU ROOF OK EXCEPT AT CORRECTIONS
09/13/2011 PLUMBING - INTERMEDIATE Cancelled IVRS - RI canceled