Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T11CM01115
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/15/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
07/11/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WALK-IN BOX SEALS TO BE NON COMBUSTIBLE 2) HANDY BOXES OVER FILLED 3) PROTECT CONDUCTORS ENTERING BOX, ALSO NEED RACEWAYS FOR CONDUCTORS 4) MOVE GROUND LUG OFF OF ISOLATION STRAP AT XFMR 5) MAINTAIN SAFE WORKING SPACE IN FRONT OF DISCONNECTS 6) PLEASE VERIFY LISTING AND LABELING OF SUMP PUMP 7) CANNOT SPLICE CORDS 8) BOND METAL PLATE OF FIXTURES IN WALKIN 9) FILL UNUSED OPENINGS IN FIXTURES |