Permit: T11CM01105

Parcel: 11202033P


Addresses:

2000 E ROGER RD E


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T11CM01105

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/27/2011 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
06/10/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/18/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TO COVER DUCT FIRST FLOOR
2) OK TO COVER DUCT 2ND FLOOR
05/16/2011 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEAL ALL DUCT JOINTS, INCLUDING ROUND TAPS
2) ALL PVC PIPE AND JOINTS ARE TO HAVE PRIMER PRIOR TO GLUE, PRIMER IS TO BE PURPLE IN COLOR PER UPC
3) PRIMARY AND SECONDARY CONDENSATE DRAINS CANNOT TERMINATE AT SAME LOCATION, SECONDARY TO TERMINATE IN A CONSPICOUS LOCATION, BUT NOT TO CAUSE DAMAGE TO THE BLDG OR BLDG COMPONENTS
4) ALL TEARS IN LINE SET INSULATION ARE TO BE REPAIRED TO AVOID CONDENSATION LEAKS
5) REPAIR HOLE IN FLOOR BETWEEN UPPER AND LOWER LEVELS UNDER RETURN PLENIUM
6) ALL DUCT IS TO BE INSULATED (NEW)
7) THIS REPORT IS NOT TO LEAVE BLDG UNTIL FINAL APPROVAL
05/13/2011 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) MAINTAIN WORKING CLEARANCES AT SERVICE
2) LABEL METER SCOCKETTE UNIT
3) PLEASE VERIFY WHICH GROUNDING CONDUCTOR IS CITY OF TUCSON AND REPLACE
4) SUPPORT NM CABLES AND SE CABLE ABOVE PANEL WITHIN 12", ALSO JUNCTION BOX
5) SEPERATE GROUNDS AND NEUTRALS AT PANEL
6) MAINTAIN FIRE SEPERATION
7) BOND JUNCTION BOX ENCLOSURE AND TERMINATE EQUIPMENT GROUNDING CONDUCTOR
8) FINISH PANEL RELOCATION