Permit: T11CM01082

Parcel: 13414019C


Addresses:

7777 E 22ND ST 03

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/28/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
12/13/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
1) ALL EXPOSED DUCT WORK TO BE INSULATED WITH 2" DUCT LINER AS NOTED ON PREVIOUS INSPECTION
2) EXPOSED PVC STILL NOT COATED
3) PAY A REINSPECTION FEE PRIOR TO NEXT INSPECTION
08/08/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ALL EXPOSED DUCT ON ROOF TO BE INSULATED WITH R8 INSULATION
2) 1/2" DUCT LINER NOT ALLOWED ANY WHERE
3) SEAL THE OPEN KNOCKOUT ON DISCONNECT TO A/C UNIT
4) PAINT ALL EXPOSED PVC WITH LATEX PAINT