Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/20/2011 | MECHANICAL - INTERMEDIATE | Approved | PER MECH FINAL | |
| 05/31/2011 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 05/25/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) DUCT JOINTS NOT SEALED 2) BALANCE SYSTEMS TO WITHIN 5 PERCENT PER PLANS 3) PROVIDE H.E. TAPS PER PLANS 4) PROVIDE DUCT SMOKE DETECTOR TEST 5) PLANS CALL FOR FACTORY INSTALLED DUCT SMOKE DETECTORS, PROVIDE APPROVAL FROM ENGINEER FOR DUCT MOUNTED APPLICATION |
|
| 05/13/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) RELOCATE DUCT SMOKE DETECTERS TO AN APPROVED LOCATION, REFER TO INSTALLATION INSTRUCTIONS. 2) REVISE PLANS TO REFLECT WORK BEING DONE 3) EXHAUST DUCT IS COMPRESSED PROVIDE PROPER ROUTING OF DUCT 4) PROVIDE GUARD RAIL AT RTU'S 5) SEAL DUCT WORK |