Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2011 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 07/15/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/01/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK TO COVER DUCT ABOVE CEILING AT RESTROOM ENTRY |
|
| 06/30/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SUPPLY AIR DUCT TO RESTROOMS IS TO BE INSULATED, INSULATION TO HAVE VAPOR BARRIER 2) FLEX DUCT NOT TO BE SUPPORTED BY CONDUIT OR OTHER PIPING 3) OK FOR TILES MECH ONLY ON EAST WALL OFFICES |