Permit: T11CM01012

Parcel: 116193700

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T11CM01012

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/14/2011 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
1) #3 INSPECTION 6-30-11 DEVIDERS NOT SHIELDS ARE NEEDED
2) NEED LETTER WITH NEW ENGRGY LOAD CALUCS FOR LIGHTNGS
3) BOXES MORE THAN 1/4" OR 1/8" 314.20 &21
4) REVISE PANEL DIRECTORIES - * NEED TO TEST FOR CIRCUIT
5) PROPERLY SUPPORT M/C CABLE FOR EF-1
6) CONTRACTOR/RELAY NOT LISTED PART - ONLY ROCONIZED COMPORT
07/01/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/16/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ABS TEST OK
2) WATER OK
3) OK TO COVER S.T.O.I.
06/15/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) SEE NOTE #2 FROM 06/02/11
2) CLEANOUTS MAY NOT BE INSTALLED IN THE HORIZONTAL POSITION
3) PLUMBERS TAPE NOT APPROVED STRAP
4) ISOLATE ABS FROM METAL STUDS
5) PROVIDE LETTER ACCEPTING ABS IN LIEU OF PVC