Permit: T11CM00998

Parcel: 108213200

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/22/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/02/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) ONLY ONE CONDUCTOR PER BREAKER TERMINAL PANEL LA
2) PROPERLY SUPPORT UNITSTRUT FROM STRUCTURE NOT CONDUIT
3) NEED OLD INSPECTION CARD ON SITE
4) RECEIVED CHECK #004946 FOR $165.00
09/22/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BOND JUNCTION BOXES, ENCLOSURES AND GUTTERS
2) TIGHTEN LOOSE FITTINGS
3) SECURE CABLE TO TRAY UPON EXITING 392.6 (C)
4) BOXES RE-WORKED DRYWALL MORE THAN 1/4" 314.20
5) EXISTING VDV CABLING TO BE PER 725.3 &8, 760.3 & 24, 770.3 & 24, 800.0 & 24 AND 300.11
6) PLEASE PROVIDE INSTRUCTIONS FOR PASS THRU OF FIRE RATED WALLS
7) USE APPROVED MOUNTING HARDWARE FOR DEVICES AND PLUG MOLD
8) COIL OF CABLING LAYING ON GRID
9) NEED DISCONNECTING MEANS FOR A/C UNIT 1D?F ROOMS
10) BONDING CONDUCTOR IN RACEWAY 800.100 (A) (6) 250.64 (E)
11) USE CORRECT SIZED LUGS FOR CONDUCTORS PANEL "LA" (PANEL FEEDER NOT PER PLAN)
12) NEED PANEL DIRECTORIES 408.4
13) CONDUCTOR COLORS IN RACEWAY TO BE PER CITY AMENDMENTS
14) OK 2ND FLOOR WEST BLDG COMPUTER LABS
15) LOOSE ROOF FITTINGS