Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/22/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/02/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) ONLY ONE CONDUCTOR PER BREAKER TERMINAL PANEL LA 2) PROPERLY SUPPORT UNITSTRUT FROM STRUCTURE NOT CONDUIT 3) NEED OLD INSPECTION CARD ON SITE 4) RECEIVED CHECK #004946 FOR $165.00 |
|
| 09/22/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BOND JUNCTION BOXES, ENCLOSURES AND GUTTERS 2) TIGHTEN LOOSE FITTINGS 3) SECURE CABLE TO TRAY UPON EXITING 392.6 (C) 4) BOXES RE-WORKED DRYWALL MORE THAN 1/4" 314.20 5) EXISTING VDV CABLING TO BE PER 725.3 &8, 760.3 & 24, 770.3 & 24, 800.0 & 24 AND 300.11 6) PLEASE PROVIDE INSTRUCTIONS FOR PASS THRU OF FIRE RATED WALLS 7) USE APPROVED MOUNTING HARDWARE FOR DEVICES AND PLUG MOLD 8) COIL OF CABLING LAYING ON GRID 9) NEED DISCONNECTING MEANS FOR A/C UNIT 1D?F ROOMS 10) BONDING CONDUCTOR IN RACEWAY 800.100 (A) (6) 250.64 (E) 11) USE CORRECT SIZED LUGS FOR CONDUCTORS PANEL "LA" (PANEL FEEDER NOT PER PLAN) 12) NEED PANEL DIRECTORIES 408.4 13) CONDUCTOR COLORS IN RACEWAY TO BE PER CITY AMENDMENTS 14) OK 2ND FLOOR WEST BLDG COMPUTER LABS 15) LOOSE ROOF FITTINGS |