Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/22/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/05/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 08/01/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 07/26/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PRPERLY SECURE AND SUPPORT RACEWAYS 2) FINISH CABLE TRAY AND RACEWAYS BONDING 3) BLDG INSPECTOR TO LOOK AT FIRE STOPPING |
|
| 07/21/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) JUNCTION BOXES TO BE ACCESSIBLE 2) NO MORE THAN 360 DEGREE IN CONDUIT RUNS 3) OK WALLS IDF1,IDF4,IDF2 AND IDF3 |
|
| 07/11/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK AS MARKED-LIBRARY, MULTI PURPOSE AND ADMINISTRATION |
|
| 06/27/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK PREVIOUS CORRFCTION 2) OK 2ND FLOOR WEST BLDG |
|
| 06/22/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) VDV CABLING TO BE PER 725.3 & 8, 760.3 & 24, 770.3 & 24, 800.3 & 24 AND 300.11 2) OPEN JUNCTION BOXES 3) CONDUIT CUT POSSIBLY DURING DEMO 4) OK WALLS ROOMS 22-25 |