Permit: T11CM00987

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T11CM00987

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/17/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK ELECTRIC
05/16/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/13/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NOTES #3 & 4
05/11/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LV LIGHTING TRANSFORMER IS UNLISTED. IT IS MARKED AS A COMPONENT OF A SIGN
2) USE BREAKERS LISTED BY MANUFACTURE
3) TRAC LIGHTING WAS NOT CODE COMPLIANT AT TIME OF INSTALL-PROPERLY SUPPORT TRACS AND ELECTRICAL CONNECTOR NOT INSTALLED INTO LIVE END
4) SECURE AND SUPPORT LV CABLING FOR NEW LIGHTING 725.24
5) NEED COVER PLATES AND INSTALL FLOOR BOX COVER
04/25/2011 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*