Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T11CM00987
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/17/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK ELECTRIC |
|
05/16/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
05/13/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NOTES #3 & 4 |
|
05/11/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LV LIGHTING TRANSFORMER IS UNLISTED. IT IS MARKED AS A COMPONENT OF A SIGN 2) USE BREAKERS LISTED BY MANUFACTURE 3) TRAC LIGHTING WAS NOT CODE COMPLIANT AT TIME OF INSTALL-PROPERLY SUPPORT TRACS AND ELECTRICAL CONNECTOR NOT INSTALLED INTO LIVE END 4) SECURE AND SUPPORT LV CABLING FOR NEW LIGHTING 725.24 5) NEED COVER PLATES AND INSTALL FLOOR BOX COVER |
|
04/25/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |