Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T11CM00959

Parcel: 111020440

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
10/07/2011 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
05/17/2011 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
1) UNIT DATA PLATE AS IDENTIFIED BY INSTALLER SHOWS MAX FUSE SIZE 35 AMPS, THE FUSES INSTALLED ARE 45 AMP, AS NOTED ON 5/9/11
2) A REFEE WILL BE ATTACHED TO THIS PERMIT
05/09/2011 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*