Permit: T11CM00957

Parcel: 125110590


Addresses:

3566 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T11CM00957

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/08/2011 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
11/03/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) DUCT ABOVE CEILING AT SALES RESTROOMS OK TO COVER
10/28/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) DUCT AT PARTS COUNTER OK TO COVER
09/22/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PLAN CALL FOR THE NEW GRILLS AND REGISTERS TO BE RE-BALANCED TO MATCH EXISTING AIR FLOWS, SINCE THESE PLANS DO NOT REFLECT ANY CFM DATA. I WILL NOT BE LOOKING FOR AN AIR BALANCE REPORT, IF THE ENGINEER IS LOOKING FOR SPECIFIC CFM'S, THEY SHOULD BE LISTED ON PLANS. THIS DOES NOT INCLUDE EXHAUST FAN DATA
2) SEE BLDG INSPECTOR FOR TEMP CLEANOUT IN SERVICE AREA ONLY
07/29/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) DUCT ABOVE CEILING IN SERVICE AREA-OK TO COVER