Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T11CM00946
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/01/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 05/31/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 05/26/2011 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/25/2011 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) SINCE THE NEW RESTROOM EXHAUST IS TIED INTO AN EXISTING DUCT SYSTEM, THE AIR BALANCE ON THE RESTROOMS SHOULD BE READ WHILE BOTH EXHAUST FANS ARE RUNNING 2) PROVIDE MINIMUM 75 CFM EXHAUST AND MAINTAIN NEG PRESSURE IN RESTROOMS THRU BALANCE OF SUPPLY AND EXHAUST |