Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T11CM00943
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/12/2011 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
07/01/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) RP INSTALL REQUIRES A UNION, PLAN SPECIFIES A WILKINS 975 XL 2) A TUCSON WATER PERMIT AND CERTIFICATION TEST IS ALSO REQUIRED 3) HB REQUIRES A VACUUM BREAKER 4) OPEN FRONT SEAT REQUIRED 5) LETTER NEEDED FOR CHANGES TO PLAN SPECIFICATIONS, IE..LAV CARRIER |