Permit: T11CM00943

Parcel: 121113250


Addresses:

4897 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T11CM00943

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/01/2011 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
05/31/2011 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
CODES DO NOT ALLOW THIS INSTALLATION.
A VENT PIPE MAY NOT BE USED A AS WASTE PIPE. 311.4
ALSO RUBBER COUPLINGS AND FITTINGS AR NOT APPROVED
05/20/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) 1 1/2" TRAP ARM MAY ONLY EXTEND 3' 6" FROM THE TRAP WEIR TO THE POINT OF VENT
2) 1 1/2" GALVANIZED 90 DEGREE ELBOW IS NOT A DRAINAGE FITTING
3) 1 1/2" TRAP ARM TO MAINTAIN 1/4" PER FOOT PITCH