Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T11CM00915
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/27/2011 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
06/22/2011 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) LV CABLING TO BE ABANDONED IF NOT IN USE, OTHER CABLING TO BE SUPPORTED TO STRUCTURE PER 725-800 NEC 2) LAY IN FIXTURES TO BE SECURED TO GRID-2 SISMEC WIRES EACH 3) PLUG UNUSED OPENINGS IN J-BOXES |
|
06/21/2011 | ELECTRIC - ABOVE CEILING | Cancelled | CANCELLED PER (SUPERINTENDENT) RENE #850-4632 | |
06/21/2011 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |