Permit: T11CM00896

Parcel: 10510010D

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T11CM00896

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/05/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*1) SUPPORT M/C & FLEX PER 300.11 ABOVE & BELOW FLOOR
2) SUPPORT VDV CABLEING PER 725.52,24, 800.24, 300.11 ABOVE & BELOW FLOOR
3)BOX OVER FILLED
4)BOXES MORE THAN 1/4" OR 1/8" 314.20 & 21