Permit: T11CM00892

Parcel: 10709092A


Addresses:

515 W KELSO ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
08/23/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROTECT CONDUIT END WITH BUSHINGS
2) NOTE 314.20 IN CEILING TILES
3) MAINTAIN SPERATION OF CHANNELS
4) FILL UNUSED PROTIONS OF GUTTERS
5) CAN NOT USE DRYWALL SCREWS FOR SUPPORT
6) SEAL UNUSED CONDUIT OPENINGS
08/18/2011 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
08/03/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
08/01/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
07/29/2011 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
07/27/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK LID MDF1
2) JUNCTION BOX TO BE ACCESSIBLE
07/26/2011 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
07/25/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
07/21/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*