Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T11CM00874

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
06/08/2011 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
06/06/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. AT TRANSFORMER : BOND GBC TO NBUTRAL,MOVE GROUND LUG OFF OF ISULATION STRAP
2. CAN NOT USE SHEET METAL THREAD SCREWS FOR GROUNDING 250.8
3. CLEAN SURFACE UNDER LUG 250.12
4. FINISH #4 PREVIOS INSPECTION
06/03/2011 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) VDV TO BE PER 300.11 725.3 & 8, 800.3 & 24, 760.24
2) SUPPORT TRAC LIGHT 2 PER 4' AND LESS/1 PER 4' OVER
3) FILL UNUSED OPENINGS IN BOXES
4) TRANSFORMER GROUNDING ELECTRODE CONDUCTOR TO BE PER 250.64 (E) AND 300.11
5) PROPERLY SUPPORT M/C NOT BLACK TAPE AND INDEPENDENTLY
05/23/2011 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) VDV CABLING TO BE PER 725.3 & 8, 800.3 & 24 AND 300.11
2) COLOR OF CONDUCTOR TO BE PER AMENDMENT 310.5 CANNOT MIX COLORS
3) GROUND WIRE TO BE 3/4 OF A TURN UNDER SCREW
4) TIGHTEN LOOSE FITTINGS
5) FILL UNUSED OPENINGS IN BOXES
6) PROTECT PVC CONDUITS AT BASE PLATES
7) OK TO POUR FLOOR