Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T11CM00874
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/08/2011 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
06/06/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. AT TRANSFORMER : BOND GBC TO NBUTRAL,MOVE GROUND LUG OFF OF ISULATION STRAP 2. CAN NOT USE SHEET METAL THREAD SCREWS FOR GROUNDING 250.8 3. CLEAN SURFACE UNDER LUG 250.12 4. FINISH #4 PREVIOS INSPECTION |
|
06/03/2011 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) VDV TO BE PER 300.11 725.3 & 8, 800.3 & 24, 760.24 2) SUPPORT TRAC LIGHT 2 PER 4' AND LESS/1 PER 4' OVER 3) FILL UNUSED OPENINGS IN BOXES 4) TRANSFORMER GROUNDING ELECTRODE CONDUCTOR TO BE PER 250.64 (E) AND 300.11 5) PROPERLY SUPPORT M/C NOT BLACK TAPE AND INDEPENDENTLY |
|
05/23/2011 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VDV CABLING TO BE PER 725.3 & 8, 800.3 & 24 AND 300.11 2) COLOR OF CONDUCTOR TO BE PER AMENDMENT 310.5 CANNOT MIX COLORS 3) GROUND WIRE TO BE 3/4 OF A TURN UNDER SCREW 4) TIGHTEN LOOSE FITTINGS 5) FILL UNUSED OPENINGS IN BOXES 6) PROTECT PVC CONDUITS AT BASE PLATES 7) OK TO POUR FLOOR |