Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T11CM00874
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/09/2011 | ELECTRIC - INTERMEDIATE | Approved | PER ELECTRIC FINAL | |
06/08/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) BOXES MORE THAN 1/4" 314.20 2) CANNOT USE DRY WALL SCREW FOR GROUNDING 250.8 3) NEED DISCONNECTING MEANS FOR FLOURESCENT FIXTURES 410.73 (G) 4) NEED ACCESS TO FLOURESCENTS AT CASH WRAP BACK |
|
05/24/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK ROUGH WALLS |
|
05/23/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
05/18/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) PLEASE VERIFY M/C TERMINATIONS FOR USAGE WITH PLASTIC BOXES |