Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
| Date |
Description |
Inspector |
Results |
Comments |
| 06/22/2012 |
FIRE SPKLR - OH PIPING & HYDRO |
|
Approved |
|
| 11/07/2011 |
FIRE SPKLR - OH PIPING & HYDRO |
|
Partial Approval |
Temporary standpipe to 3rd floor in bldg. 1 approved 200 psi test for 2 hours still need to add more standpipe as bldg. goes up to 5 story. Also psi tested and checked 6" inch pipe to tee that will go to parking level to FDC. Need to install FDC signs on fence by road showing where FDC is at. |