Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
Permit Number - T11CM00868
Inspection Description - FIRE SPKLR - OH PIPING & HYDRO
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/22/2012 | FIRE SPKLR - OH PIPING & HYDRO | Approved | ||
11/07/2011 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | Temporary standpipe to 3rd floor in bldg. 1 approved 200 psi test for 2 hours still need to add more standpipe as bldg. goes up to 5 story. Also psi tested and checked 6" inch pipe to tee that will go to parking level to FDC. Need to install FDC signs on fence by road showing where FDC is at. |