Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T11CM00845
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/16/2012 | FIRE - FINAL | Approved | Weekend fire final inspection | |
09/14/2012 | FIRE - FINAL | Denied | 1.) Replace painted sprinkler heads in white open ceiling areas. 2.) Correct sprinkler coverage under duct work, (Dillards side and main entrance area). 3.) Correct sprinkler coverage by windows looking at Dillards (small pocket). 4.) Repair leaking sprinkler head in show case window area to mall. 5.) Add exit sign over exit door just south of the mall entrance. 6.) Need all stair wells illuminated with 120v lighting and emergency battery back up lighting. 7.) Do not call for final until all painting is done. |
|
06/06/2012 | FIRE - FINAL | Partial Approval | Okay to use level one for sales | |
06/05/2012 | FIRE - FINAL | Denied | Need partial given for alarm and final given for sprinkler before a partial will be given for level one floor to be used for sales. |