Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T11CM00845
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/05/2012 | FIRE SPKLR - FINAL | Approved | PER FIRE FINAL | |
09/14/2012 | FIRE SPKLR - FINAL | Denied | 1.) Replace painted sprinkler heads in white open ceiling areas. 2.) Correct sprinkler coverage under duct work, (Dillards side and main entrance area). 3.) Correct sprinkler coverage by windows looking at Dillards (small pocket). 4.) Repair leaking sprinkler head in show case window area to mall. 5.) Add exit sign over exit door just south of the mall entrance. 6.) Need all stair wells illuminated with 120v lighting and emergency battery back up lighting. 7.) Do not call for final until all painting is done. |
|
06/06/2012 | FIRE SPKLR - FINAL | Partial Approval | Approval for level one only | |
06/05/2012 | FIRE SPKLR - FINAL | Denied | 1. Need spare heads in head boxes 2. Need sprinkler wrenches in boxes 3. Need FDC caps 4. Need to check sprinkler heads in the show cases |