Permit: T11CM00845

Parcel: 10511061P


Addresses:

4510 N ORACLE RD


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T11CM00845

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/05/2012 FIRE SPKLR - FINAL Approved PER FIRE FINAL
09/14/2012 FIRE SPKLR - FINAL Denied 1.) Replace painted sprinkler heads in white open ceiling areas.
2.) Correct sprinkler coverage under duct work, (Dillards side and main entrance area).
3.) Correct sprinkler coverage by windows looking at Dillards (small pocket).
4.) Repair leaking sprinkler head in show case window area to mall.
5.) Add exit sign over exit door just south of the mall entrance.
6.) Need all stair wells illuminated with 120v lighting and emergency battery back up lighting.
7.) Do not call for final until all painting is done.
06/06/2012 FIRE SPKLR - FINAL Partial Approval Approval for level one only
06/05/2012 FIRE SPKLR - FINAL Denied 1. Need spare heads in head boxes
2. Need sprinkler wrenches in boxes
3. Need FDC caps
4. Need to check sprinkler heads in the show cases