Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T11CM00845
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/12/2012 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
06/07/2012 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* TESTED 1ST FLOOR DUCT SMOKE DECTECTORS |
|
06/06/2012 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* DRAIN PANS DO NOT FIT PROPERLY UNDER AIR HANDLERS. FAN COIL DISCONNCETERS ARE OVER FUSED. PROVIDE HOSE CLAMPS ON PLASTIC PUMP HOSES. PROVIDE A LETTER FROM MANUFACTURE THAT STATES THESE PUMPS ARE OK TO BE INSTALLED IN A SHEET METAL BOX. ALL AIR HANDLERS THAT SHARE A COMMON RETURN ? . MUST BE INTERLOCKED FOR FAN SHEET DOWN IF ANY DUCT SMOKE DETECTOR IS IN ALARM |
|
06/04/2012 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
06/01/2012 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |