Permit: T11CM00845

Parcel: 10511061P


Addresses:

4510 N ORACLE RD


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T11CM00845

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/12/2012 MECHANICAL - FINAL Approved IVRS - Inspection :*
06/07/2012 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
TESTED 1ST FLOOR DUCT SMOKE DECTECTORS
06/06/2012 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
DRAIN PANS DO NOT FIT PROPERLY UNDER AIR HANDLERS. FAN COIL DISCONNCETERS ARE OVER FUSED. PROVIDE HOSE CLAMPS ON PLASTIC PUMP HOSES. PROVIDE A LETTER FROM MANUFACTURE THAT STATES THESE PUMPS ARE OK TO BE INSTALLED IN A SHEET METAL BOX. ALL AIR HANDLERS THAT SHARE A COMMON RETURN ? . MUST BE INTERLOCKED FOR FAN SHEET DOWN IF ANY DUCT SMOKE DETECTOR IS IN ALARM
06/04/2012 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
06/01/2012 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*