Permit: T11CM00799

Parcel: 10511061F


Addresses:

4530 N ORACLE RD

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/09/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) FINISH #2, 3 & 5
11/07/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLEASE VERIFY EQUAL LENGTHS OF PARALLEL CONDUCTORS
2) VERIFY TERM BLOCK IN CHILLER-NOT LISTED PART
3) PLEASE PROVIDE BREAKER PAPERWORK FOR OLD SWITCHBOARD
4) NEED PLANS ON SITE
5) PROPERLY SUPPORT M/C CABLES FOR CONTROL WIRING
6) REMOVE OR JUNCTION OFF OLD WIRING
10/20/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLEASE HAVE ELECTRICIAN PRESENT TO OPEN EQUIPMENT FOR INSPECTION
2) CHILLER AND PUMPS ENERGIZED WITHOUT CLEARANCES