Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/09/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FINISH #2, 3 & 5 |
|
| 11/07/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLEASE VERIFY EQUAL LENGTHS OF PARALLEL CONDUCTORS 2) VERIFY TERM BLOCK IN CHILLER-NOT LISTED PART 3) PLEASE PROVIDE BREAKER PAPERWORK FOR OLD SWITCHBOARD 4) NEED PLANS ON SITE 5) PROPERLY SUPPORT M/C CABLES FOR CONTROL WIRING 6) REMOVE OR JUNCTION OFF OLD WIRING |
|