Permit: T11CM00789

Parcel: 13510150R

Inspection Status: Approved

Inspection History: PLUMBING - ABOVE CEILING

Date Description Inspector Results Comments
07/01/2011 PLUMBING - ABOVE CEILING Approved IVRS - Inspection :*
06/30/2011 PLUMBING - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) SECURE THE CLOSET FLANGE TO THE FLOOR PRIOR TO SETTING THE STOOL AND PROVIDE AN OPEN FRONT SEAT
2) PROVIDE ROOF ACCESS AND CEILING ACCESS AT FUTURE INSPECTION
06/29/2011 PLUMBING - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
06/21/2011 PLUMBING - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONDENSATE DRAIN PIPING CANNOT DRAIN INTO A SANITARY VENT
2) PROVIDE APPROVED SUPPORT FOR ALL OVERHEAD PIPING
3) SEE INSPECTION HISTORY DATED 6/1/11 ON SITE