Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/29/2011 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 06/21/2011 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LOW VOLTAGE PIPES MISSING PLASTIC BUSHING 110.14A 2) OUTLET IN BATHROOM TO BE GFI 210.8-B1 3) J-BOX IN BATHROOM HAS ROMEX WIRE NOT TO BE USED IN TEE-BAR CEILING 334.12-A2 4) OUTLET QUAD IN BATHROOM MISSING SCREWS 406.4-C 5) EXIT NOT WORKING PROPERLY WHEN POWER SHUT OFF 700.17 |