Permit: T11CM00788

Parcel: 11615077H

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T11CM00788

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/29/2011 FIRE - FINAL Approved
06/28/2011 FIRE - FINAL Denied 1. Correct sprinkler coverage in back roomhead is 9' 9" off wall can only be 9' off wall using 800 sq ft room rule or 7' 6" off wall.
2. Need up to date sprinkler inspection done last one on file 06/03/2009 all of property.
3. Need 5 year check valve inspection done last one on file 09/01/2000 all of property.