Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T11CM00788
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/29/2011 | FIRE - FINAL | Approved | ||
| 06/28/2011 | FIRE - FINAL | Denied | 1. Correct sprinkler coverage in back roomhead is 9' 9" off wall can only be 9' off wall using 800 sq ft room rule or 7' 6" off wall. 2. Need up to date sprinkler inspection done last one on file 06/03/2009 all of property. 3. Need 5 year check valve inspection done last one on file 09/01/2000 all of property. |