Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/29/2011 | FIRE - FINAL | Approved | ||
| 06/28/2011 | FIRE - FINAL | Denied | 1. Correct sprinkler coverage in back roomhead is 9' 9" off wall can only be 9' off wall using 800 sq ft room rule or 7' 6" off wall. 2. Need up to date sprinkler inspection done last one on file 06/03/2009 all of property. 3. Need 5 year check valve inspection done last one on file 09/01/2000 all of property. |