Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T11CM00788
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/09/2011 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 06/08/2011 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection 1) NO WORK PROGRESS 2) PLEASE PAY REINSPECTION FEE BEFORE NEXT INSPECTION |
|
| 06/07/2011 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) TRACK LIGHTING REQUIRES SISMEC SUPPORT TO STRUCTURE 2) NOTE 1 LAST INSPECTION |
|
| 05/25/2011 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROTECT VDV CABLE FROM SHARP METAL EDGES 2) SUPPORT CONDUITS DOWN WALL 3) OLD RECESSED CANS LAYING ON TIELS-REMOVE 4) OPEN JUNCTION BOXES 5) PROTECT CABLING IN WALLS 6) M/C LAYING ON GRID 7) RECEPT LAYOUT NOT PER PLANS |