Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/23/2011 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 05/09/2011 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 04/14/2011 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/07/2011 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE TO ALSO PROVIDE PHYSICAL PROTECTION FOR #8 CONDUCTORS 2) NEED TO LABEL ELECTRICAL EQUIPMENT 3) PROPERLY INSTALL REDUCING WASHERS 4) PROTECT CONDUCTORS 300.4 5) GROUNDING ELECTRODE CONDUCTOR TO TERMINATE TO GROUNDED CONDUCTOR 250.24 6) PLEASE VERIFY PERMIT FOR NEW ELECTRIC WIRING IN SHED 7) LABEL CIRCUITS PER 408.4 8) SUPPORT RISER/CONDUITS UP WALL 9) NEED GUY BACK BRACING FOR RISER 10) PLEASE HAVE ELECTRICIAN PRESENT TO OPEN ELECTRICAL EQUIPMENT |