Permit: T11CM00734

Parcel: 11011174J


Addresses:

2480 N ARCADIA AV

Inspection Status: Approved

Inspection History: MECHANICAL - HYDRONIC PIPING

Date Description Inspector Results Comments
07/07/2011 MECHANICAL - HYDRONIC PIPING Approved IVRS - Inspection :*
06/20/2011 MECHANICAL - HYDRONIC PIPING Partial Approval IVRS - Inspection :*
1) HYDRO TEST AT 100 PSI PLUS OK
06/16/2011 MECHANICAL - HYDRONIC PIPING Not ready for Inspection IVRS - Inspection :*
1) HYDONIC PRESSURE TEST IS TO BE 1 1/2 TIMES OPERATING PRESSURE OR 100 PSI WHICH EVER IS GREATER, TEST IS TO BE WITH WATER NOT AIR
2) DUCT ABOVE HARD LIDS 100D AND 100E OK TO COVER