Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HYDRONIC PIPING
Permit Number - T11CM00734
Inspection Description - MECHANICAL - HYDRONIC PIPING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/07/2011 | MECHANICAL - HYDRONIC PIPING | Approved | IVRS - Inspection :* | |
06/20/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) HYDRO TEST AT 100 PSI PLUS OK |
|