Permit: T11CM00733

Parcel: 12402002B


Addresses:

1818 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T11CM00733

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/13/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
09/08/2011 PLUMBING - FINAL Not ready for Inspection 1) ALL PIPING IS TO BE NEW AND CLEAN
2) INDIRECT WASTE PIPING MADE OF PVC TO BE PRIMED AND SOLVANT CEMENTED IN AN APPROVED MANNER
3) CONNECTIONS TO EQUIPMENT PIPING TO BE CLAMPED
4) FIX LEAKS AND INSULATE CONDENSATE PIPING TO PREVENT SWEATING
09/06/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) INDIRECT WASTE PIPING MAY NOT BE COMBINED
2) PVC PIPE REQUIRES THE USE OF PURPLE PRIMER AND SOLVANT CEMENT
3) SECURE MIXING VALVES
4) SECURE PVC INDIRECT WASTE PIPING
08/19/2011 PLUMBING - FINAL Partial Approval
08/18/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
CONTRACTOR WISHING TO OCCUPY LOBBY - NO PLUMBING ISSUES HERE.
08/17/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) REPAIR MADE AT BACKWATER VALVE OK
2) EACH WATER SUPPLIED DEVICE TO HAVE ITS OWN BACK FLOW DEVICE. SPLITTING DOWNSTREAM NOT PERMITTED