Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/19/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* CIRCUITS 21 & 23 WERE NOT CODE COMPLIANT AT TIME OF INSTALL |
|
| 08/16/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FINISH MAKE UP AND VERIFY BOX FILL 2) VERIFY BOX FILL FOR HANDY BOXES FOR OUTLETS 314.16 (A) + (B) 3) FINISH #1 & 3 PREVIOUS INSPECTION 4) OK TO TILE ELECTRIC, EXCEPT AS NOTED |
|
| 08/10/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK RESTROOMS HARD LIDS |
|
| 08/09/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SUPPORT M/C CABLE PER CODES 330.30 AND 300.11 2) SUPPORT VDV CABLING PER CODES 725.3 & 8M 800.3 & 24 AND 300.11 3) CORDS NOT ALLOWED ABOVE CEILINGS 400.7 & 8 4) CONDUIT SEPERATED AND NOT SUPPORTED |
|
| 07/27/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK FRAME WALLS (ELECT) |