Permit: T11CM00733

Parcel: 12402002B


Addresses:

1818 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T11CM00733

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/19/2011 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
CIRCUITS 21 & 23 WERE NOT CODE COMPLIANT AT TIME OF INSTALL
08/16/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) FINISH MAKE UP AND VERIFY BOX FILL
2) VERIFY BOX FILL FOR HANDY BOXES FOR OUTLETS 314.16 (A) + (B)
3) FINISH #1 & 3 PREVIOUS INSPECTION
4) OK TO TILE ELECTRIC, EXCEPT AS NOTED
08/10/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK RESTROOMS HARD LIDS
08/09/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) SUPPORT M/C CABLE PER CODES 330.30 AND 300.11
2) SUPPORT VDV CABLING PER CODES 725.3 & 8M 800.3 & 24 AND 300.11
3) CORDS NOT ALLOWED ABOVE CEILINGS 400.7 & 8
4) CONDUIT SEPERATED AND NOT SUPPORTED
07/27/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK FRAME WALLS (ELECT)