Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T11CM00660
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/21/2011 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
09/20/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) MAKE CORRECTIONS AT WATER HEATER PER NOTES FROM 8/18/11 AND PROVIDE AN APPROVED HANGER FOR VENT AT HAND SINK ON NORTH WALL BY INTERCEPTOR |
|
08/18/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NEED TO SEE RPB DRAINS, BACKFLOW CERTS ON SITE 2) PROVIDE FACTORY TAPEPD CLEANOUT PLUGS WITH MACHINE SCREWS TO HOLD IN CLEANOUT COVERS 3) NEW WATER HEATER REQUIRES CORRECT VENTING SOLVENT WELD FITTINGS (NOT NO HUB COUPLING) 4) EXTEND VENT SYSTEM TO 3' ABOVE AIR INTAKE WITH APPROVED PIPING 5) T & P RELIEF DRAIN TO GRAVITY DRAIN TO APPROVED RECEPTOR WITH 1" AIR GAP 6) PROVIDE SEPERATE DRAIN FOR FILTER SYSTEM INTO JANITOR SINK WITH 1" AIR GAP 7) CAP OFF OLD CONNECTION INTO CONDENSATE DRAIN FROM WATER HEATER AND PROVIDE APPROVED CONDENSATE DRAIN FROM WATER HEATER 8) PROVIDE TEMPERING FOR PUBLIC USE LAVS |